CDN 3425 Rental - Teseq Burst/EFT Coupling Clamp

Capcitive Coupling Clamp

CDN 3425 Rental - Teseq Burst/EFT Coupling Clamp

Coupling Clamp (CCL) Features 

      • New design, Includes Safety Cover & Interlock
      • ISO 17025 Calibration & 2 Days Free Transit
      • Compliant IEC 61000-4-4 Ed.2 & Ed.3
      • Can Work With Many Immunity Generators!
      • Replaces CDN 8014 and CDN 8015
      • Turnkey Solution - Arrives Ready for Testing!

Overview

The Teseq CDN3425 (Teseq CCL) main purpose is to couple Burst/EFT pulses to data lines. It can also be used to couple to mains lines where no CDN is available; for example, high current lines >200 A. This coupling decoupling network (CDN) capacitive coupling clamp (CCL) comes with an ISO 17025 accredited calibration and works with a many conducted immunity generators

The new design is fully compliant with the specifications of IEC 61000-4-4 Ed 2.0 2004, as well as with the draft of EN/IEC 61000-4-4 Ed 3.0 to be published in 2012. This model also replaces earlier models CDN 8014 and CDN 8015.The coupling capacitance between the coupling clamp and the cable laid in it depends on the cable characteristics. 

Coupling Clamp (CCL) Features 

      • New design, Includes Safety Cover & Interlock
      • ISO 17025 Calibration & 2 Days Free Transit
      • Compliant IEC 61000-4-4 Ed.2 & Ed.3
      • Can Work With Many Immunity Generators!
      • Replaces CDN 8014 and CDN 8015
      • Turnkey Solution - Arrives Ready for Testing!

Overview

The Teseq CDN3425 (Teseq CCL) main purpose is to couple Burst/EFT pulses to data lines. It can also be used to couple to mains lines where no CDN is available; for example, high current lines >200 A. This coupling decoupling network (CDN) capacitive coupling clamp (CCL) comes with an ISO 17025 accredited calibration and works with a many conducted immunity generators

The new design is fully compliant with the specifications of IEC 61000-4-4 Ed 2.0 2004, as well as with the draft of EN/IEC 61000-4-4 Ed 3.0 to be published in 2012. This model also replaces earlier models CDN 8014 and CDN 8015.The coupling capacitance between the coupling clamp and the cable laid in it depends on the cable characteristics. 

Data SheetUser Manual

Common Standards

EN/IEC 61000-4-4

Max. permissible burst voltage

8 kV

Usable length of the clamp

1000mm

Diameter of the test cable:

4 to 40 mm

Connectors

SHV-NIM female, 50 Ω (on both ends)

Distance to the earth reference plane

100 mm

Dimensions

1100 x 200 x 110mm, 43.31 x 7.78 x 4.33in

Weight

7.5kg, 16.53lbs