Description
Hipot & Ground Tester Features
- 5kV AC, 6kV DC, Hipot, Ground, & Insulation Tester
- Compact & Easy to Use Bench Top Unit
-
Ideal for Dielectric Withstand & Insulation Tests
- Includes Capabilities of Hypot 3805 & 3865 series
- Free Technical Support & 2 Days Free Transit
Overview
The new Hypot® Series raises the bar for safety and efficiency in production line Hipot Testers. Whether your application requires AC Withstand tests, DC Withstand tests, or Insulation Resistance tests, The Hypot Series Hipot Tester provides innovations that will allow you to begin achieving best practices for safety and efficiency without the need for an expensive automated test system or connection to a PC. Stop handwriting thousands of test results and improve traceability with on-board data storage and data transfer capabilities.
Automate your production line with direct barcode connection, which allows you to quickly associate products with pre-programed test files. Keep operators safe with SmartGFI®, Safety Interlock, and PPE compatible accessories. You can even connect the Hypot® Series with the HYAMP® Series to form a seamless safety compliance system for Hipot and Ground Bond Testing. The Hypot Series includes the following models: 3805, 3865, 3870.
Specifications
Input Specifications |
|
Voltage |
100 – 120 VAC / 200 – 240 VAC ± 10% Auto Range |
Frequency |
50/60 Hz ± 5% |
Fuse |
3.15 A, Fast Blow 250 VAC |
Dielectric Withstand Test Mode |
|
Output Rating |
5 kVA @ 20 mAAC 6 kVA @ 7.5 mADC (3865/3870 only) |
Maximum Limit |
AC Range: 0.00 – 20.00 mA Resolution: 0.01 mA DC Range: 0 – 7500 µA Resolution: 1 µA Accuracy: AC and DC ± (2% of setting + 2 counts) |
Minimum Limit |
AC Range: 0.000 – 9.999 mA Resolution: 0.001 mA DC Range: 0.0 – 999.9 µA Resolution: 0.1µA Accuracy: AC and DC ± (2% of setting + 2 counts) |
Frequency |
Range: 1-9, ON/OFF Select |
Ground Fault Interrupt |
GFI Trip Current: 450 µA max (AC or DC), Fixed HV Shut Down Speed: < 1 msec |
Current Display |
AC Range 1: 0.000 – 4.000 mA Range 2: 3.50 – 20.00 mA DC Range 1: 0.0 µA – 400.0 µA Range 2: 0.350 mA – 4.000 mA Range 3: 3.50 mA – 7.50 mA Accuracy: All Ranges ± (2% of reading + 2 counts) |
DC Output Ripple |
≤ 5% Ripple rms at 6 kVDC @ 7.5 mA Resistive Load |
RAMP-HI Selectable |
Range: 0.0 – 7,500 µA, User Selectable |
Charge-LO |
0 – 350 µA DC or Auto Set |
Peak Short Circuit Current |
< 50 msec for no load, < 100 msec for capacitive load The maximum capacitive load vs. output voltage: 1µF < 1KV 0.08µF < 4KV 0.75µF < 2KV 0.04µF < 5KV 0.5µF < 3KV 0.015uF < 6KV |
Insulation Resistance Test Mod |
|
Voltage Setting |
Range: 30 – 1,000 VDC Resolution: 1 V Accuracy: ±(2% of setting + 5 V) |
Resistance Display |
Range: 1 – 50,000 MΩ |