EM Test DPA 500N - Rent Harmonics & Flicker Power Analyzer

Digital Harmonics & Flicker Analyzer:

  • Compliant Analysis to IEC 61000-3-2/3 
  • Maximum 530V rms & 16A Continuous
  • Real-time Data Acquisition with Software
  • Built-in Lumped Flicker Impedance
  • ISO 17025 Calibration & Laptop Included

Get weekly, two week, and monthly rentals on all products

Got Questions about the equipment? Get technical support

Two FREE days transit time with every rental

Request A Quote

Harmonics & Flicker Rental Equipment

Description

Overview

Harmonics and interharmonics are caused by modern electronic power conditioning modules. Such, mostly non-linear, modules to control loads and to reduce power consumption is the source of voltage at unwanted frequencies superposed on the supply voltage.

Voltage fluctuations caused by varying load currents may influence the luminance or the spectral distribution of lighting systems. The impression of the unsteadiness of visual sensation induced by this light stimulus is called flicker. The DPA500N harmonics and flicker analyzer is used for single phase applications.

Data Sheet User Manual

Specifications

Common Standards

IEC/EN 61000-3-2IEC/EN 61000-3-3

IEC/EN 61000-3-12 with Ext. CT

Measuring System 


Input channels

2 (1x current & 1x voltage)

Frequency range

15Hz - 3,000Hz

A/D converter

16 Bit

Controller

 Embedded processor Pentium 200MHz

Signal processor

Motorola DSP

Memory

Internal hard disk

Category

Class I as per IEC/EN 61000-4-7

Voltage Input


Input range

10V - 530V rms

Overload

 4,000V peak

Accuracy

Better than 0.4% of reading

Current Input

Input range internal

16A continuous, 50A short time

Accuracy internal

Better than 0.4% of reading Better than 0.05% rel. to 16A

Input range external

Depending on CT model used. With optionally delivered CT max. 140A

Accuracy external CT

Related to 16A 2 turns better than 0.8% 5 turns better than 0.6%

General Data


Temperature

0°C - 40°C

Rel. humidity

10% - 90%, non-condensing

Power supply

 85V - 255V, 47Hz - 63Hz

Power

Max. 50W

Dimension

19" 3HU: 133mm x 449mm x 500mm

Weight

13kg

Insulation

Input to case 3kV rms

Interface

USB for control and data transfer

Harmonics Analysis 


As per

 IEC/EN 61000-3-2 Ed5.1 JIS C 61000-3-2 (2019) IEC/EN 61000-3-12 with ext. CT

Design as per

IEC/EN 61000-4-7 Ed.2.1 and IEC/EN 61000-4-7 Ed.1

Harmonics

1st - 50th order

Grouping

IEC/EN 61000-4-7 for Interharmonics

Synchronization

PLL; accuracy better than 0.005%

Measuring window

Rectangular window with 8, 10, 12 or 16 periods)

Algorithm

FFT

Smoothing filter

 1st order 1,5s digital low pass filter (on/off), selectable

Anti-aliasing filter

> 90dB

Measurement duration

More than 30 hours, limited by the capacity of the hard-disk (approx. 1MB/min of measuring data)

Display

Vrms, Irms, Ipeak, Vpeak

Harmonics

V, I, Phase, P, Q, S (2nd - 50th order)

Power information

P, Q, S, Power factor, THD(V), THD(I), Crest factor(V), Crest factor(I)

Flicker Analysis
As per

IEC/EN 61000-3-3 Ed3 A2

Design as per

IEC/EN 61000-4-15 230V , 50/60 Hz and 120V , 50/60 Hz

Flicker impedance (built-in)

Line: 0.24ohm + j0.15ohm

Neutral: 0.16ohm + j0.10ohm

Accuracy Pst and Plt

Better than 5%

Accuracy dmax, dc, dt

Better than 5%, according IEC 61000-4-15

Flicker data

Pst and Plt, Vrms, dmax, dc, dt P50%S, P10%S, P3%S, P1%S, P0.1%

Maximum values

Pst, dmax, dc, dt

Observation period

Min. 1min, selectable

You may also like